An FX9R031 repeater and FX9R032 extender can extend the AS-i transmission distance by up to 100m respectively. Up to 2 repeaters can be connected in series. The 2 lines (segments) connected to a repeater are insulated and those connected to an extender are not.
| . |
The power supply status of the 2 lines connected to a repeater is indicated on the repeater. |
|

FX9R031
(KAF99-107) |
|
|
| |
| Type |
Repeater
FX9R031 |
Extender
FX9R032 |
| Power supply |
Supplied from AS-i line |
| Power consumption from the AS-i cable |
Up to 100mA per AS-i line |
| Insulation between AS-i LINE1 and LINE2 |
Insulated |
Not insulated |
| Indication |
AS-i power supply LINE1 and LINE2: Green LED |
| Cable extension length |
100m (Total distance: up to 300m,
using 2 repeaters in series) |
Up to 100m, 1 extender only |
| Mounting method |
Rail/screw dual mounting |
| Accessory |
Mounting plate |
| Mass |
Approx. 200g (including mounting plate) |
|

Repeater
Since the two cables connected to a repeater R are isolated each other, an AS-i power supply must be installed between repeaters.
In one AS-i system, up to 2 repeaters can be connected in series, and multiple repeaters in parallel.
The total maximum AS-i cable length is 100m that can be connected to an AS-i power supply.
The AS-i transmission distance can be extended up to 300m if up to 100m AS-i cable per segment is connected in series.
(Please consult with Fuji Electric FA when you intend to use 2 repeaters in series.)
Extender
No AS-i slaves and AS-i power supplies cannot be installed between the AS-i master and extender E.
The cable length is max. 100m.
Extenders cannot be connected in parallel.
The total maximum AS-i cable length is 100m that can be connected to an AS-i power supply.
The AS-i transmission distance can be extended up to 300m if up to 100m AS-i cable per segment is connected in series.
(Please consult with Fuji Electric FA when you intend to use an extender and repeater in series.)
|