Fe e-Front runners FUJI ELECTRIC FA COMPONENTS & SYSTEMS
 
   
Top Product Infomation Technical Infomation Sales Infomation Corporate Guide Contact US Site Map
Sales Distribution
After Service Network
What is AS-i?
Products
Master
Slave
Safety at Work
AS-i Cable
AS-i Power Supply
Accessories
Download
Inquiries
Site Map
AS-i Top page
FUJI AS-Interface_AS-i Masters Masters
DeviceNet/AS-i gateway
Description

The DeviceNet/AS-i gateway converts data between the open network DeviceNet and the AS-Interface protocol. DeviceNet was developed and is supported by the Open DeviceNet Vendor Association (ODVA).

. Up to 62 A/B slaves can be connected.
. Up to 31 analog slaves can be connected.
. Addition of notification function of peripheral error.
. Being upward compatible with the conventional FC2L-DL conforming to AS-i specifications V2.0, replacement is easy.
. The slaves' configuration can be registered by a pushbutton switch on the front of the gateway.
. The status of the AS-i bus is indicated by the LEDs on the DeviceNet/AS-i gateway, e.g., showing disconnection of slaves, AS-i power supply failure, and automatic addressing availability.
. The 7-segment LED indicates the addresses of disconnected slaves (in protected mode) and configured slaves (in configuration mode).
. AS-i specification: V2.1

FC2LA-DL
(KK03-044)

Ratings and specifications
General specifications
Type FC2LA-DL
Insulation resistance
(Communication sections excluded)
10M or more with 500V DC megger, between external terminals connected together and FG
Dielectric strength
(Communication sections excluded)
445V AC for 1min, between external terminals connected together and FG
Operating temperature 0 to +55˚C (no icing or no condensation)
Storage temperature –20 to +70˚C (no icing or no condensation)
Relative humidity 20 to 90% RH (no condensation)
Pollution degree Pollution degree 2 (no conductive dust)
Atmosphere No corrosive gases and massive dust
Vibration resistance * Amplitude: 0.15mm
Constant acceleration: 19.6m/s2
for 2 hours in each direction
Shock resistance * 294m/s2 destruction threshold
(Peak acceleration)
Noise immunity Noise simulator method: Rise
time 1ns, pulse width 1μs,
1.5kVp-p
Electrostatic discharge resistance Contact discharge method: ±6kV,
Aerial discharge method: ±8kV
Degree of protection (IEC 60529) IP20 (installation inside panel)
Mounting method IEC rail/screw dual mounting
Cooling method Natural cooling
Mass Approx. 320g
Approval CE
Note: * Resistance where the DeviceNet/AS-i gateway is screw-mounted. Less vibration and shock are permitted when IEC rail-mounted.

DeviceNet communications
Applicable DeviceNet specification Release 2.0
Power supply for communication 24V DC (operating voltage range:
11 to 25V DC)
Current consumption 80mA or less
Type of node Group2 Only Server
Vendor ID 0x13F (Fuji Electric)
Device type Communication adapter (Code: 0x0C)
Station number setting (MAC
address)
64 stations with numbers from 01
to 63, but no overlaps of number
Cable
length
Transmission speed 500kbps 250kbps 125kbps
Trunk line
Drop line
Total drop line
100m
6m
39m
250m
6m
78m
500m
6m
156m
No. of message connection
No. of I/O connection
1 (Pre-defined master/slave connection set)
1 (Polling)
No. of Transmission data
(fragmentized)
8/16/32/26/42 bytes (Mode 0 to 4 changeable)
No. of Receiving data
(frgmentized)
8/16/32/26/42 bytes (Mode 0 to 4 changeable)
Cable Dedicated DeviceNet cable

AS-i communications
Maximum connectable slaves 62 A/B slaves for V2.1 (addresses 1A to 31A, 1B to 31B)
31 standard slaves for V2.0
(addresses 1 to 31, Analog slaves /standard slaves.)
Maximum No. of input/output
points
434 points (When connecting A/B slaves: 248 input and 186 output points)
248 points (When connecting standard slaves: 124 input and 124 output points)
Network topology Tree, line, and star structure
Maximum cable length Up to 100m (extendable up to 300m via Repeaters)
Transminssion speed 167kbps
Transmission cable AS-i cable (yellow) or parallel
cable (2 x 1.5mm2)
Cycle time Approx. 10 (5) ms (with 62 (31)
slaves connected)
Power supply for communication AS-i power supply (30V DC)
AS-i current consumption 120mA or less

Page top