| Type |
NJ-ASL |
| AS-i communications |
Maximum connectable slaves |
31 (Max. points per slave: 4 inputs, 4 outputs) |
| Maximum No. of input/output points |
248 points (Input: 124/Output: 124) |
| Network topology |
Tree, line, and star structure |
| Max. cable length |
Up to 100m (extendable up to 300m via repeaters) |
| Transmission speed |
167kbps |
| Transmission cable |
AS-i cable (yellow), or parallel cable (2 x 1.5mm2) |
| Cycle time |
Max. 5ms (with 31 slaves) |
| Power supply for communications |
AS-i power supply (30V DC) |
| AS-i current consumptions |
100mA or less |
| NJ series interface |
No. of slots occupied |
1 (mountable on the CPU base unit) |
| Internal current consumption (at 5V) |
250mA or less |
| General specifications |
Insulation resistance |
10M or more with 500V DC megger, between external terminals and FG |
| Dielectric strength |
1500V AC for 1min, between external terminals and FG |
| Operating temperature |
0 to +55˚C (no icing or no condensation) |
| Storage temperature |
–20 to +70˚C (no icing or no condensation) |
| Relative humidity |
20 to 95% RH (no condensation) |
| Pollution degree |
2 (no conductive dust) |
| Atmosphere |
No corrosive gases, no organic solvent adhering to the master |
| Vibration resistance |
Amplitude: 0.15mm, constant acceleration: 19.6m/s2 for 2 hours in each direction |
| Shock resistance |
294m/s2 destruction threshold (Peak acceleration) |
| Noise immunity |
Noise simulator method: Rise time 1ns, pulse width 1µs, 1.5kVp-p |
| Electrostatic discharge resistance |
Contact discharge method: ±8kV, aerial discharge method: ±15kV |
| Degree of protection (IEC 60529) |
IP30 (installation inside panel) |
| Cooling method |
Natural cooling |
| Mass |
Approx. 230g |
| Approval |
— |