FUJI AS-Interface_AS-i Masters Masters
T-link/AS-i gateway
Description

The FC2L-TL T-link/AS-i gateway converts data between a proprietary network T-link and the AS-i protocol. The T-link was developed and is supported by Fuji Electric Co., Ltd.

. The slaves' configuration can be registered by a pushbutton switch on the front of the gateway.
. The status of the AS-i bus is indicated by the LEDs on the T-link/AS-i gateway, e.g., showing disconnection of slaves, AS-i power supply failure, and automatic addressing availability.
. The 7-segment LED indicates the addresses of disconnected slaves (in protected mode) and configured slaves
(in configuration mode).
. Simple connection reduces man-hours.
. AS-i specification: V2.0

FC2L-TL
(KK01-298A)

Ratings and specifications
General specifications
Type FC2L-TL
Insulation resistance
(Communication sections excluded)
5M or more with 500V DC megger, between external terminals connected together and FG
Dielectric strength
(Communication sections excluded)
1500V AC for 1min, between external terminals connected together and FG
Operating temperature 0 to +55˚C (no icing or no condensation)
Storage temperature -20 to +70°C (no icing or no condensation)
Relative humidity 20 to 90% RH (no condensation)
Pollution degree Pollution degree 2 (no conductive dust)
Atmosphere No corrosive gases and massive dust
Vibration resistance * Amplitude: 0.15mm
Constant acceleration: 19.6m/s2
for 2 hours in each direction
Shock resistance * 294m/s2 destruction threshold
(Peak acceleration)
Noise immunity Noise simulator method: Rise time 1ns, pulse width 1µs, 1.5kVp-p
Electrostatic discharge resistance Contact discharge method: ±6kV, Aerial discharge method: ±8kV
Degree of protection (IEC60529) IP20 (installation inside panel)
Mounting method IEC rail/screw dual mounting
Cooling method Natural cooling
Mass Approx. 320g
Approval -
Note: * Resistance where the T-link/AS-i gateway is screw-mounted. Less vibration and shock are permitted when IEC rail-mounted.

T-link communication
Station number setting 00 to 99
Transmission speed 500kbps
Maximum transmission distance 1000m with T-link cable
No. of words occupied Input 8W/output 8W = Total 16 words
Network topology Daisy chain
Cable Shielded twist pair cable

AS-interface communications
Maximum connectable slaves 31 (with addresses from 1 to 31)
Max. points per slave: 4 inputs, 4 outputs
Maximum No. of input/output
points
248 points (Input: 124/Output: 124)
Network topology Tree, line, and star structure
Maximum cable length 100m (extendable up to 300m via
Repeater)
Transmission speed 167kbps
Transmission cable AS-i cable (yellow) or parallel cable (2 x 1.5mm2), (also used as power cable)
Cycle time Max. 5ms (with 31 slaves)
Power supply for communication Use of AS-i power supply (30V DC)
AS-i current consumption 120mA or less

Input power specifications
Supply voltage (permissible range) 24V DC (19 to 30V DC)
Power consumption Max. 3.3W
Retention at power failure
Inrush current Approx. 8A