Safety monitor
The safety monitor is the core device of AS-i Safety (Safety at Work).
The configuration of safety-related devices connected to the safety monitor is defined by the PC. A unique control mode according to the combination is selectable with the definition on the PC.
For example, emergency stop, electromagnetic lock safety door switch, two-handed operation, and category 0 or category 1 stop can be selected.
The monitor can be controlled using the AS-i address in order to make full use of the AS-i diagnostic function.

The following two types of monitor control are possible.
A safety monitor with one 2-channel operating circuit.
A safety monitor with two 2-channel operating circuits.


Enhanced safety monitor
With the enhanced safety monitor support more functions. A larger work memory facilitates configuration of com- plex applications. Transient shutdowns are stored in a buffer for diagnostic pur- poses. Logical functions can be com- bined with one another and cascaded. Additional timers for ON and OFF delays as well as pulse functions have also now been integrated.

Safety monitor
(KK04-119)

Features
Monitors safe stations and links safe inputs
Ensures safe shutdown
Modular design to suit individual requirements
Single or 2-channel isolation circuits
With safety outputs for safety category 4 (EN954-1 ) or SIL3 (IEC 61508) and stop category 0 or stop category 1
Integrated ON and OFF delays, pulse function, extended work memory


Specifications Type
Basic Safety Monitor One isolation circuit 3RK1105-1AE04-0CA0
Two isolation circuit 3RK1105-1BE04-0CA0
Enhanced Safety Monitor One isolation circuit 3RK1105-1AE04-2CA0
Two isolation circuit 3RK1105-1BE04-2CA0
Sealable cap 3RP1902
Configuration software 3RK1802-2FB06-0GA0
Cable set (safety monitor to personal computor) 3RK1901-5AA00