Fe e-Front runners FUJI ELECTRIC FA COMPONENTS & SYSTEMS
 
   
Top Product Infomation Technical Infomation Sales Infomation Corporate Guide Contact US Site Map
Sales Distribution
After Service Network
What is AS-i?
Products
Master
Slave
Safety at Work
AS-i Cable
AS-i Power Supply
Accessories
Download
Inquiries
Site Map
AS-i Top page
FUJI AS-Interface_AS-i Slave Slaves
AS-i motor starter slave, Standard Slave
Description

The FE16D slave incorporates a reversing motor starter for up to 2.2kW, having a sturdy IP65 structure to make it suitable for severe environmental conditions. The FE16D can be used outside the control panel, thus helping to reduce the number of relay boxes and the size of the panel.

. The starter slave can be easily connected to the ASInterface flat cable by insulation piercing connectors.
. The power cable can be easily connected by a single-action connector.
. A translucent door, which can be padlocked, simplifies addressing and resetting.
. Designed for versatile application, with a motor range of 0.1 to 2.2kW at 200V AC and a thermal overload relay range of 0.1 to 7A.
. AS-i specification: V2.0

FE16D-SJ13RGNE12
(KK01-136A)

Ratings and specifications
Type
FE16D-SJ13RG*E12
Built-on thermal overload relay: * N: TR-0NZ716, E: TK-0NZ716
Motor capacity:
…20 to 25 (0.1 to 2.2kW)
Heat element:
…A to V (0.1-0.15A to 7.0-11.0A) at 200V AC

0.1kW 0.1-0.15A
0.15-0.24A
0.24-0.36A
0.36-0.54A
0.48-0.72A
0.2kW 0.64-0.96A
0.8-1.2A
0.95-1.45A
20 A
20 C
20 E
20 G
20 H
21 J
21 K
21 L

0.4kW 1.4-2.2A
1.7-2.6A
0.75kW 2.2-3.4A
2.8-4.2A
1.5kW 4.0-6.0A
5.0-8.0A
2.2kW 6.0-9.0A
7.0-11.0A
22 M
22 N
23 P
23 R
24 S
24 T
25 U
25 V
Slave type Standard slave
Number of inputs/outputs 4 inputs /4 outputs (IN3, IN4, OUT3, OUT4: not in use)
AS-Interface profile (I/O, ID) 7, F
Operating voltage (in acc. with AS-Interface specification) 26.5 to 31.6V DC
Current consumption 50mA DC or less

Ratings and specifications (Continued)
Degree of protection (IEC60529) IP65
Connector for power cable See page 95 for recommended cables.
Operating temperature 0 to +55˚C (no icing or no condensation)
Storage temperature −25 to +70˚C (no icing or no condensation)
Connection of communication cable Via yellow AS-i cable by piercing connector
External power supply method Via black AS-i cable by piercing connector
Electrical protection
for AS-Interface
Reverse polarity protection
Electrostatic discharge resistance


Electromagnetic field noise immunity
Burst noise
Built-in
Contact discharge method: ±4kV, Aerial discharge method: ±8kV, IEC61000-4-2
(Class B)
80 to 1000MHz, Electric field strength: 10V/m, IEC61000-4-3 (Class A)
2kV (Class B)/1kV (Class A), IEC61000-4-4
Shock resistance (IEC68-2-27) 50m/s2 (11ms)
Vibration resistance (IEC68-2-6) 10 to 55Hz, 0.25mm one-way amplitude
Mass Approx. 2.2kg (including mounting plate)
Addressing method Can be made with an addressing unit (FL1HA-E) via addressing cable (FX9Y002) connected to the addressing jack on the slave front. Connecting the addressing cable to a slave will disconnect the slave from the AS-Interface.
Approval CE

Page top