FUJI AS-Interface_AS-i Slave Slaves
Waterproof slave (Flat type) FM6DB1, A/B Slave Standard Slave

Description
The slave inclueds an upper section, which is the actual slave, and a lower section, which is the mounting plate. The IP67 structure provides excellent environmental resistance. By allowing use outside the control panel, the slave eliminates the need for relay boxes and contributes to downsizing. The slave is also flatter than conventional slaves and reduces restrictions on installation.

The depth, including the mounting plate, is only 30mm, which is 15mm flatter than conventional models.
The actual slave can be easily fixed to the mounting plate using one screw.
Mounting plates are available in two types: IEC rail/screw dual mounting and exclusive screw mounting.
Slave addressing is done by connecting an addressing unit to the front of the slave.
LED indication of external power supply (2I/2O and 4O models only)
Both NPN and PNP models are available.
The slave can be easily connected to the AS-i flat cable by insulation piercing connection.
Short-circuit protection is provided for the sensor power supply and output circuit.
Actuators and sensors can be easily connected by singleaction M12 connectors (IEC60947-5-2).
Two outputs or inputs per M12 connector.
Conforms to EC Directive ENC Directive (No. 89/336/EEC); EN50081-1, EN61000-6-2 (EN50082-2).
AS-i specification: V2.1

(KKD05-246)

Ratings and specifications
Type
(actual slave)
NPN model
PNP model
FM6DB1-40XXN
FM6DB1-40XXP
FM6DB1-03TNX
FM6DB1-03TPX
Slave type A/B slave
Number of inputs/outputs 4 inputs 3 outputs
AS-Interface profile (I/O, ID, ID2) *1 0, A, 2 8, A, 2
Operating voltage (in accordance with AS-i specification) 26.5 to 31.6V DC
Current
consumption
Slave only
Including sensors
45mA DC or less
245mA DC or less
45mA DC or less
Notes: *1 The initial value of ID1 is 7 (variable from 0 to 7).


  Specifications Type
Actual Slaves    NPN, 4 inputs, 200mA FM6DB1-40XXN
PNP, 4 inputs, 200mA FM6DB1-40XXP
NPN, 3 outputs, 1A FM6DB1-03TNX
PNP, 3 outputs, 1A FM6DB1-03TPX
Mounting Plate    Rail/screw dual mount, AS-i FM6B1-04FK
Rail/screw dual mount, AS-i and 24VDC FM6B1-04FE
Screw mount, AS-i FM6B2-04FK
Screw mount, AS-i and 24CDC FM6B2-04FE

Page top